Nominal Voltage (max system voltage) :
3.5/6 kV (7.2 kV)
6/10 kV (12 kV)
8.7/15 kV (17.5 kV)
12/20 kV (24 kV)
18/30 kV (36 kV)
Specification :
SPLN 43-5-3 : 1995
Construction :
Conductor | : | Copper or Allumunium ( Compact Circular Stranded ) | ![]() |
|
Conductor Screen | : | Extruded Semiconductive Compound | ||
Insulation | : | Extruded Crosslink Polyethylene (XLPE) | ||
Insulation Screen | : | Extruded Strippable Semiconductive Compound | ||
Water Blocking | : | Helicaly Overlapped Semiconductive Water blocking tape | ||
Metalic Screen | : | Helicaly Overlapped Copper Wire | ||
Water Blocking | : | Helicaly Overlapped Non-conductive Water blocking tape | ||
Sheath | : | Extruded PVC 90o C grade |
Symbol | : | |
Applicable Standard | : | Other Specification are available on request |
Application | : | Suitable for distribution Indoor and Outdoor Installation, in conduit, troughs or on Trays |
N2XSY & NA2XSY
COPPER OR ALUMUNIUM CONDUCTOR, XLPE INSULATED,
COPPER WIRE SCREENED AND PVC SHEATED
Nominal Voltage : 12/20 kV
Maximum System Voltage : 24 kV
Specification : SPLN 43-5-3 : 1995
Other specification are available on request
NA2XSY - ALUMUNIUM CONDUCTOR |
(SINGLE CORE) |
|||||||||||||
Nominal cross sectional area | mm2 | 35 | 50 | 70 | 95 | 120 | 150 | 185 | 240 | 300 | 400 | 500 | 630 | |
Conductor | Approx. diameter | mm | 6,9 | 7,9 | 9,6 | 11,3 | 12,7 | 14 | 15,7 | 18 | 20,1 | 22,9 | 26,2 | 29,7 |
Max. DC resistance at 20 C | Ohm/km | 0,868 | 0,641 | 0,443 | 0,32 | 0,253 | 0,206 | 0,164 | 0,125 | 0,1 | 0,0778 | 0,0605 | 0,0469 | |
Insulation | Nominal thicknes | mm | 5,5 | 5,5 | 5,5 | 5,5 | 5,5 | 5,5 | 5,5 | 5,5 | 5,5 | 5,5 | 5,5 | 5,5 |
Min. DC resistance at 20 C | m.ohm.km | 4400 | 4100 | 3600 | 3200 | 3000 | 2800 | 2500 | 2300 | 2100 | 1900 | 1700 | 1500 | |
Nominal sheath thickness | mm | 3 | 3 | 3 | 3 | 3 | 3 | 3 | 3 | 3 | 3 | 3 | 3.2 | |
Overall diameter | Approx. | mm | 30 | 31,1 | 32,7 | 34,4 | 35,8 | 37,1 | 38,8 | 41,1 | 43,2 | 46,4 | 49,7 | 53,6 |
Cable Net. Weight | Approx. | kg/km | 927 | 1000 | 1113 | 1243 | 1362 | 1554 | 1714 | 1947 | 2182 | 2613 | 3022 | 3582 |
Standar length per reel | m | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 500 | |
Minimum bending radius | mm | 360 | 373 | 392 | 413 | 430 | 445 | 466 | 493 | 518 | 557 | 596 | 643 | |
Capacitance | uF/km | 0,144 | 0,157 | 0,177 | 0,197 | 0,214 | 0,229 | 0,249 | 0,276 | 0,3 | 0,332 | 0,371 | 0,411 | |
Inductance | mH/km | 0,178 | 0,163 | 0,144 | 0,129 | 0,119 | 0,112 | 0,103 | 0,093 | 0,085 | 0,077 | 0,069 | 0,062 | |
Current carrying | in air | A | 180 | 217 | 240 | 328 | 378 | 425 | 485 | 513 | 652 | 740 | 838 | 873 |
Capacity at 30 C | in ground | 158 | 187 | 228 | 271 | 307 | 339 | 380 | 439 | 491 | 543 | 617 | 657 | |
Short circuit current at 1 sec. | kA | 3,2 | 4,6 | 6,4 | 8,7 | 11 | 13,8 | 17 | 22,1 | 27,6 | 36,8 | 46 | 58 | |
AC Voltage test | kV/5 Min | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 |