Nominal Voltage (max system voltage) :
3.5/6 kV (7.2 kV)
6/10 kV (12 kV)
8.7/15 kV (17.5 kV)
12/20 kV (24 kV)
18/30 kV (36 kV)
Specification :
IEC 60502- 2 : 2005
Construction :
Conductor | : | Copper or Allumunium ( Compact Circular Stranded ) | ![]() |
|
Conductor Screen | : | Extruded Semiconductive Compound | ||
Insulation | : | Extruded Crosslink Polyethylene (XLPE) | ||
Insulation Screen | : | Extruded Strippable Semiconductive Compound | ||
Metalic Screen | : | Helicaly Overlapped Copper Tape | ||
Filler | : | PP Yarm | ||
Binding Tape | : | Helicaly Overlapped Polyester Tape | ||
Outer Sheath | : | PVC 90o C grade |
Symbol | : | |
Applicable Standard | : | Other Specification are available on request |
Application | : | Suitable for Distribution indoor and outdoor Installation, in conduit, trough or on Trays or for laying in the ground where not sustain mechanical damage. |
N2XSEY & NA2XSEY SINGLE JACKET
COPPER OR ALUMUNIUM CONDUCTOR, XLPE INSULATED,
COPPER TAPE SCREENED AND PVC SHEATED
Nominal Voltage : 3.6/6 kV
Maximum System Voltage : 7,2 kV
Specification : IEC 60502-2 : 2005
Other specification are available on request
NA2XSEY - ALUMUNIUM CONDUCTOR |
|||||||||||||
Nominal cross sectional area | mm2 | 10 | 16 | 25 | 35 | 50 | 70 | 95 | 120 | 150 | 185 | 240 | |
Conductor | Approx. diameter | mm | 3,6 | 4,6 | 5,8 | 6,8 | 7,9 | 9,6 | 11,3 | 12,7 | 14 | 15,7 | 18 |
Max. DC resistance at 20 C | Ohm/km | 3,08 | 1,91 | 1,2 | 0,868 | 0,641 | 0,443 | 0,32 | 0,253 | 0,206 | 0,164 | 0,125 | |
Insulation | Nominal thicknes | mm | 2,5 | 2,5 | 2,5 | 2,5 | 2,5 | 2,5 | 2,5 | 2,5 | 2,5 | 2,5 | 2,6 |
Min. DC resistance at 20 C | m.ohm.km | 3700 | 3200 | 2800 | 2500 | 2200 | 1900 | 1700 | 1500 | 1400 | 1300 | 1200 | |
Nominal sheath thickness | mm | 1,9 | 1,9 | 2 | 2,1 | 2,2 | 2,3 | 2,4 | 2,6 | 2,7 | 2,8 | 3 | |
Overall diameter | Approx. | mm | 28,9 | 31 | 33,7 | 36,2 | 38,8 | 42,5 | 46,3 | 49,9 | 52,9 | 56,8 | 62,5 |
Cable Net. Weight | Approx. | kg/km | 792 | 920 | 1107 | 1293 | 1509 | 1844 | 2233 | 2622 | 2997 | 3499 | 4301 |
Standar length per reel | m | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 500 | 500 | |
Minimum bending radius | mm | 347 | 372 | 404 | 434 | 466 | 510 | 556 | 599 | 635 | 682 | 750 | |
Capacitance | uF/km | 0,169 | 0,195 | 0,225 | 0,25 | 0,278 | 0,32 | 0,362 | 0,397 | 0,429 | 0,471 | 0,511 | |
Inductance | mH/km | 0,151 | 0,131 | 0,114 | 0,102 | 0,092 | 0,08 | 0,071 | 0,064 | 0,06 | 0,054 | 0,05 | |
Current carrying | in air | A | 72 | 82 | 103 | 133 | 160 | 200 | 241 | 280 | 317 | 363 | 424 |
capacity at 30 C | in ground | 70 | 80 | 102 | 131 | 156 | 192 | 230 | 261 | 294 | 333 | 388 | |
Short circuit current at 1 sec. | kA | 0,9 | 1,5 | 2,3 | 3,2 | 4,6 | 6,4 | 8,7 | 11 | 13,8 | 17 | 22,1 | |
AC Voltage test | kV/5 Min | 12,5 | 12,5 | 12,5 | 12,5 | 12,5 | 12,5 | 12,5 | 12,5 | 12,5 | 12,5 | 12,5 |