Suitable for distribution Indoor and Outdoor Installation, in conduit, troughs or on Trays or for laying in the ground where not sustain mechanical damage
Nominal Voltage (max system voltage) :
3.5/6 kV (7.2 kV)
6/10 kV (12 kV)
8.7/15 kV (17.5 kV)
12/20 kV (24 kV)
18/30 kV (36 kV)
Specification :
IEC 60502- 2 : 2005
Construction :
Conductor | : | Copper or Allumunium ( Compact Circular Stranded ) | |
Conductor Screen | : | Extruded Semiconductive Compound | |
Insulation | : | Extruded Crosslink Polyethylene (XLPE) | |
Insulation Screen | : | Extruded Strippable Semiconductive Compound | |
Metalic Screen | : | Copper Wire and Tape | |
Sheath | : | Extruded PVC 90o C grade |
Symbol | : | N2XCY |
Applicable Standard | : | Other Specification are available on request |
Application | : | Suitable for distribution Indoor and Outdoor Installation, in conduit, troughs or on Trays or for laying in the ground where not sustain mechanical damage |
N2XCY
COPPER CONDUCTOR, XLPE INSULATED,
CONCENTRIC CONDUCTOR AND PVC SHEATED
Nominal Voltage : 3.6/6 kV
Maximum System Voltage : 7,2 kV
Specification : IEC 60502-2 : 2005
Other specification are available on request
N2XCY - COPPER CONDUCTOR |
(SINGLE CORES) |
||||||||||||||
Nominal cross sectional area | mm2 | 10 | 16 | 25 | 35 | 50 | 70 | 95 | 120 | 150 | 185 | 240 | 300 | 400 | |
Cross sect. area of concentris cond. | mm2 | 10 | 16 | 16 | 16 | 25 | 35 | 50 | 70 | 70 | 95 | 120 | 150 | 185 | |
Conductor | Approx. diameter | mm | 3,7 | 4,6 | 5,8 | 6,9 | 8 | 9,6 | 11,3 | 12,7 | 14,1 | 15,8 | 18,1 | 20,3 | 23,2 |
Max. DC resistance at 20 C | Ohm/km | 1,83 | 1,15 | 0,727 | 0,524 | 0,387 | 0,268 | 0,193 | 0,153 | 0,124 | 0,0991 | 0,0754 | 0,0601 | 0,047 | |
Insulation | Nominal thicknes | mm | 2,5 | 2,5 | 2,5 | 2,5 | 2,5 | 2,5 | 2,5 | 2,5 | 2,5 | 2,5 | 2.6 | 2.8 | 3 |
Min. DC resistance at 20 C | m.ohm.km | 3700 | 3200 | 2800 | 2500 | 2200 | 1900 | 1700 | 1500 | 1400 | 1300 | 1200 | 1200 | 1100 | |
Nominal sheath thickness | mm | 1,4 | 1,5 | 1,5 | 1,6 | 1,6 | 1,7 | 1,7 | 1,8 | 1,9 | 1,9 | 2 | 2,1 | 2,3 | |
Overall diameter | Approx. | mm | 15,6 | 16,8 | 18 | 19,2 | 20,7 | 22,6 | 25 | 27 | 28,6 | 31 | 34 | 36,7 | 40,8 |
Cable Net. Weight | Approx. | kg/km | 370 | 500 | 603 | 717 | 931 | 1248 | 1662 | 2103 | 2387 | 2988 | 3795 | 4667 | 5821 |
Standar length per reel | m | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | |
Minimum bending radius | mm | 188 | 202 | 216 | 231 | 249 | 271 | 300 | 323 | 343 | 372 | 407 | 441 | 490 | |
Capacitance | uF/km | 0,172 | 0,195 | 0,225 | 0,253 | 0,28 | 0,32 | 0,362 | 0,397 | 0,432 | 0,474 | 0,513 | 0,531 | 0,56 | |
Inductance | mH/km | 0,149 | 0,131 | 0,114 | 0,101 | 0,091 | 0,08 | 0,071 | 0,064 | 0,059 | 0,054 | 0,05 | 0,048 | 0,046 | |
Current carrying | in air | A | 98 | 138 | 190 | 230 | 276 | 343 | 416 | 479 | 534 | 609 | 713 | 807 | 897 |
Capacity at 30 C | in ground | 94 | 121 | 164 | 194 | 228 | 277 | 327 | 369 | 403 | 451 | 515 | 572 | 617 | |
Short circuit current at 1 sec | kA | 1,4 | 2,3 | 3,6 | 5 | 7,1 | 9,9 | 13,5 | 17 | 21,3 | 26,3 | 34,1 | 42,6 | 56,8 | |
AC Voltage test | kV/5 Min | 12,5 | 12,5 | 12,5 | 12,5 | 12,5 | 12,5 | 12,5 | 12,5 | 12,5 | 12,5 | 12,5 | 12,5 | 12,5 |